Key Specifications
GTIN: 4055626244594
Orderkey: 2907874
(General): 6 kA (for 20 A gG/B backup fuse)
Catalog page: Page 50 (C-4-2017)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
GTIN 4055626244594
Orderkey 2907874
(General) 6 kA (for 20 A gG/B backup fuse)
Catalog page Page 50 (C-4-2017)
Packing unit 1 pc
Country of origin DE (Germany)
(Connection data) (DC-) - G
Custom tariff number 85363010
(Ambient conditions) PBT-FR
(UL connection data) EN 61643-11 2012
Altitude (Dimensions) ≤ 6000 m (amsl (above mean sea level))
Type (Ambient conditions) DIN rail module, two-section, divisible
Color (Ambient conditions) light grey RAL 7035
Response time tA (General) ≤ 25 ns
SPD Type (Connection data) 1
Depth (Key Commercial Data) 74.5 mm (incl. DIN rail 7.5 mm)
Width (Key Commercial Data) 25.4 mm
(Additional technical data) 1 A DC (30 V DC)
(Standards and Regulations) For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
EN type (Ambient conditions) T2
Height (Key Commercial Data) 97.9 mm
Nominal voltage UN (General) 100 V DC ... 120 V DC
TOV behavior at UT (General) 174 V DC (5 s / withstand mode)
Residual current IPE (General) ≤ 10 µA DC
Shock (operation) (Dimensions) 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Rated load current IL (General) 40 A (Biconnect M4 fork-type cable lug 6​ mm²)
Degree of protection (Dimensions) IP20
Nominal voltage (Connection data) 120 V DC
Mounting type (Ambient conditions) DIN rail: 35 mm
Vibration (operation) (Dimensions) 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Mode of protection (Connection data) (DC+) - (DC-)
Weight per Piece (excluding packing) 209.600 g
Housing material (Ambient conditions) PA 6.6-FR 20% GF
Operating current (UL specifications) 1 A AC
Operating voltage (UL specifications) 125 V AC
Tightening torque (UL specifications) 4 lbf-in.
China RoHS (Standards and Regulations) Environmentally Friendly Use Period = 50
Horizontal pitch (Key Commercial Data) 1.4 Div.
REACh SVHC (Standards and Regulations) Lead 7439-92-1
Maximum continuous voltage UC (General) 150 V DC
Mode of protection (Ambient conditions) (DC+) - (DC-)
Degree of pollution (Ambient conditions) 2
Number of positions (Ambient conditions) 2
Screw thread (Additional technical data) M2
Screw thread (Indicator/remote signaling) M5
Standards/regulations (UL connection data) IEC 61643-11 2011
Power distribution system (Connection data) DC
Ambient temperature (operation) (Dimensions) -40 °C ... 80 °C
IEC power supply system (Ambient conditions) DC
IEC test classification (Ambient conditions) II
Short-circuit current rating ISCCR (General) 0.2 kA (without backup fuse)
Stripping length (Additional technical data) 7 mm
Connection method (Additional technical data) Plug-in/screw connection via COMBICON
Max. backup fuse with branch wiring (General) 20 A (gG / B at ISCCR> 200 A)
Operating current (Additional technical data) 5 mA AC ... 1 A AC
Operating voltage (Additional technical data) 5 V AC ... 250 V AC (Altitude ≤ 2000 m amsl)
Permissible humidity (operation) (Dimensions) 5 % ... 95 %
Stripping length (Indicator/remote signaling) 16 mm
Tightening torque (Additional technical data) 0.25 Nm
Connection method (Indicator/remote signaling) Fork-type cable lug
Nominal discharge current In (Connection data) 20 kA
Switching function (Additional technical data) PDT contact
Tightening torque (Indicator/remote signaling) 4.5 Nm
Conductor cross section AWG (UL specifications) 30 ... 14
Nominal discharge current In(8/20) µs (General) 20 kA
Tightening torque (UL indicator/remote signaling) 30 lbf-in.
Maximum continuous voltage UC (Protective circuit) 135 V AC (for operation in safety lighting systems)
Maximum discharge current Imax(8/20) µs (General) 40 kA
Total discharge current Itotal(8/20) µs (General) 40 kA
Voltage protection level Up(DC+) - (DC-) (General) ≤ 1.8 kV
Surge protection fault message (Ambient conditions) Optical, remote indicator contact
Voltage protection level Up(DC+/DC-) - PE (General) ≤ 0.85 kV
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 80 °C
Max. backup fuse with V-type through wiring (General) 20 A (gG / B at ISCCR> 200 A)
Short-circuit current rating (SCCR) (Connection data) 50 kA
Conductor cross section AWG (Additional technical data) 28 ... 16
Conductor cross section AWG (Indicator/remote signaling) 12 ... 4
Impulse discharge current (10/350) µs, charge (General) 0.5 As
Conductor cross section solid (Additional technical data) 0.14 mm² ... 1.5 mm²
Voltage protection rating VPR (DC+) - G (Connection data) 700 V
Voltage protection rating VPR (DC-) - G (Connection data) 700 V
Conductor cross section solid (Indicator/remote signaling) 2.5 mm² ... 25 mm²
Conductor cross section AWG (UL indicator/remote signaling) 10 ... 2
Flammability rating according to UL 94 (Ambient conditions) V-0
Conductor cross section flexible (Additional technical data) 0.14 mm² ... 1.5 mm²
Conductor cross section flexible (Indicator/remote signaling) 1.5 mm² ... 6 mm²
Voltage protection rating VPR (DC+) - (DC-) (Connection data) 1500 V
Impulse discharge current (10/350) µs, peak value limp (General) 1 kA
Impulse discharge current (10/350) µs, specific energy (General) 0.25 kJ/Ω

Product Description

Plug-in surge protection device, according to Type 2/Class II, for DC current sources with linear service characteristic, with remote indication contact.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top