VAL-MS BE/FM/120 - VAL-MS BE/FM/120 2908652 PHOENIX CONTACT Type 2 surge protection base element
In Stock Hot Product

VAL-MS BE/FM/120

VAL-MS BE/FM/120 2908652 PHOENIX CONTACT Type 2 surge protection base element

$0.00 USD
3266 in stock
Key Specifications
: T2
Note: For installation into a touch protected cabinet. For applications with UC> 500 V distances at the side and distances at the connection area must be minimum of 5 mm between different active parts including earthed parts.
Type: DIN rail module, two-section, divisible
Color: black (RAL 9005)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
T2
Note For installation into a touch protected cabinet. For applications with UC> 500 V distances at the side and distances at the connection area must be minimum of 5 mm between different active parts including earthed parts.
Type DIN rail module, two-section, divisible
Color black (RAL 9005)
Depth 51.5 mm (incl. DIN rail 7.5 mm)
Width 17.6 mm
Height 96.8 mm
EN type T2
Altitude ≤ 2000 m (amsl)
SPD Type 4CA
Product type Base element
Screw thread M5
Mounting type DIN rail: 35 mm
Material group I
Product family VALVETRAB MS
Connection name Remote fault indicator contact
Nominal voltage 690 V AC
Open side panel No
Article revision 07
Horizontal pitch 1 Div.
Housing material PA 6.6
Pollution degree 2
Stripping length 16 mm
Connection method Screw connection
Operating current 5 mA AC ... 1 A AC
Operating voltage 5 V AC ... 250 V AC
Shock (operation) 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Tightening torque 3 Nm (1.5 mm² ... 16 mm²)
Switching function Changeover contact
Dimensional drawing
Insulating material PA 6.6
Number of positions 1
AC operating current 1 A AC
Degree of protection IP20 (only when all terminal points are used)
Nominal frequency fN 50 Hz (60 Hz)
Overvoltage category III
CTI value of material 600
Rated load current IL 80 A
Vibration (operation) 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
IEC test classification II
Standards/specifications IEC 61643-11
Conductor cross section AWG 15 ... 2
Conductor cross section rigid 1.5 mm² ... 35 mm²
Maximum continuous voltage UC 600 V AC
Surge protection fault message Remote indication contact
Ambient temperature (operation) -40 °C ... 80 °C
Conductor cross section flexible 1.5 mm² ... 25 mm²
Permissible humidity (operation) 5 % ... 95 %
Short-circuit current rating ISCCR 25 kA
Max. backup fuse with branch wiring 125 A (gG)
Flammability rating according to UL 94 V-0
Ambient temperature (storage/transport) -40 °C ... 80 °C
Max. backup fuse with V-type through wiring 80 A (gG)

Product Description

Base element for type 2 unloaders from the VALVETRAB MS product series, with remote indication contact. Execution: 1 channel
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top