Service time: Monday to Friday 9:00-18:00
VAL-MS 385/80 ST - VAL-MS 385/80 ST 2920353 PHOENIX CONTACT Type 2 surge protection plug
In Stock Hot Product

VAL-MS 385/80 ST

VAL-MS 385/80 ST 2920353 PHOENIX CONTACT Type 2 surge protection plug

$0.00 USD
3939 in stock
Key Specifications
GTIN: 4046356157353
Note: Made to Order (non-returnable)
Orderkey: 2920353
(General): 457 V AC (120 min / withstand mode)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
GTIN 4046356157353
Note Made to Order (non-returnable)
Orderkey 2920353
(General) 457 V AC (120 min / withstand mode)
Catalog page Page 49 (C-6-2015)
Packing unit 10 pc
Country of origin DE (Germany)
(UL specifications) EN 61643-11 2012
Custom tariff number 85363030
(Ambient conditions) PBT
Altitude (Dimensions) ≤ 2000 m (amsl (above mean sea level))
Minimum order quantity 10 pc
Type (Ambient conditions) Male
Color (Ambient conditions) jet black RAL 9005
Response time tA (General) ≤ 25 ns
SPD Type (Connection data) 4CA
Depth (Key Commercial Data) 67.3 mm
Width (Key Commercial Data) 17.7 mm
EN type (Ambient conditions) T2
Height (Key Commercial Data) 47 mm
Nominal voltage UN (General) 240/415 V AC (TN-C)
TOV behavior at UT (General) 480 V AC (5 s / withstand mode)
Nom. voltage (Connection data) 240 V AC
Nominal frequency fN (General) 50 Hz (60 Hz)
Residual current IPE (General) ≤ 600 µA
Shock (operation) (Dimensions) 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Residual voltage Ures (General) ≤ 2 kV (at In)
Degree of protection (Dimensions) IP20
Mounting type (Ambient conditions) on base element
Vibration (operation) (Dimensions) 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Nominal frequency (Connection data) 50/60 Hz
Mode of protection (Connection data) L-N
Weight per Piece (excluding packing) 91.000 g
Housing material (Ambient conditions) PA 6.6
Voltage protection level Up (General) ≤ 2 kV
Connection method (Protective circuit) pluggable
Horizontal pitch (Key Commercial Data) 1 Div.
Standby power consumption PC (General) ≤ 230 mVA
Maximum continuous voltage UC (General) 385 V AC
Mode of protection (Ambient conditions) L-N
Degree of pollution (Ambient conditions) 2
Standards/regulations (UL specifications) IEC 61643-11 2011
Power distribution system (Connection data) Single phase
Ambient temperature (operation) (Dimensions) -40 °C ... 80 °C
IEC power supply system (Ambient conditions) TN-C
IEC test classification (Ambient conditions) II
Short-circuit current rating ISCCR (General) 25 kA
Max. backup fuse with branch wiring (General) 250 A (gG)
Permissible humidity (operation) (Dimensions) 5 % ... 95 %
Nominal discharge current In(8/20) µs (General) 40 kA
Maximum discharge current Imax(8/20) µs (General) 80 kA
Nominal discharge current In(L-N) (Connection data) 20 kA
Surge protection fault message (Ambient conditions) optical
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 80 °C
Measured limiting voltage MLV (L-N) (Connection data) 2710 V
Impulse discharge current (10/350) µs, charge (General) 1.25 As
Flammability rating according to UL 94 (Ambient conditions) V-0
Impulse discharge current (10/350) µs, peak value limp (General) 2.5 kA
Impulse discharge current (10/350) µs, specific energy (General) 1.56 kJ/Ω
Maximum continuous operating voltage MCOV (L-N) (Connection data) 385 V AC

Product Description

Plug-in surge protection type 2 with varistor for VAL-MS 385/80/..., with thermal control, optical defect indication.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top