Key Specifications
: T2
Note: 2011
Type: DIN rail module, two-section, divisible
Color: black (RAL 9005)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
T2
Note 2011
Type DIN rail module, two-section, divisible
Color black (RAL 9005)
Depth 55.3 mm
Width 17.5 mm
Height 52.4 mm
EN type T2
Altitude ≤ 2000 m (amsl)
SPD Type 4CA
Product type Replacement plug
Mounting type on base element
Material group I
Product family VALVETRAB MS
Nominal voltage 230 V AC
Article revision 27
Horizontal pitch 1 Div.
Housing material PA 6.6
Pollution degree 2
Response time tA ≤ 25 ns
Connection method pluggable
Nominal frequency 50/60 Hz
Shock (operation) 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Mode of protection L-N
Nominal voltage UN 240/415 V AC (TN)
TOV behavior at UT 335 V AC (5 s / withstand mode)
Dimensional drawing
Direction of action 1L-N/PE
Insulating material PA 6.6
Number of positions 1
Degree of protection IP20
Nominal frequency fN 50 Hz (60 Hz)
Overvoltage category III
Residual current IPE ≤ 0.45 mA
CTI value of material 600
Residual voltage Ures ≤ 1.35 kV (at In)
Vibration (operation) 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
IEC power supply system TN
IEC test classification II
Standards/specifications IEC 61643-11
Power distribution system Single phase
Voltage protection level Up ≤ 1.35 kV
Standby power consumption PC ≤ 120 mVA
Maximum continuous voltage UC 275 V AC
Surge protection fault message optical
Ambient temperature (operation) -40 °C ... 80 °C
Permissible humidity (operation) 5 % ... 95 %
Nominal discharge current In(L-N) 20 kA
Short-circuit current rating ISCCR 25 kA
Max. backup fuse with branch wiring 125 A (gG)
Measured limiting voltage MLV (L-N) 1910 V
Flammability rating according to UL 94 V-0
Nominal discharge current In(8/20) µs 20 kA
Ambient temperature (storage/transport) -40 °C ... 80 °C
Maximum discharge current Imax(8/20) µs 40 kA
Maximum continuous operating voltage MCOV (L-N) 275 V AC
Arrester can be tested with CHECKMASTER from software version: From SW rev. 1.10

Product Description

Plug-in type 2 surge protection with high-power varistor for VAL-MS base element, with thermal control, optical fault indication. Execution: 230 V AC
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide