Service time: Monday to Friday 9:00-18:00
VAL-CP-350-ST-GY - VAL-CP-350-ST-GY 2882718 PHOENIX CONTACT Type 2 surge protection plug
In Stock Hot Product

VAL-CP-350-ST-GY

VAL-CP-350-ST-GY 2882718 PHOENIX CONTACT Type 2 surge protection plug

$0.00 USD
3136 in stock
Key Specifications
GTIN: 4046356175869
Note: Made to Order (non-returnable)
Orderkey: 2882718
(General): 457 V AC (120 min / safe failure mode)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
GTIN 4046356175869
Note Made to Order (non-returnable)
Orderkey 2882718
(General) 457 V AC (120 min / safe failure mode)
Catalog page Page 66 (C-4-2017)
Packing unit 10 pc
Country of origin DE (Germany)
(Connection data) EN 61643-11 2012
Custom tariff number 85363010
(Ambient conditions) L-PEN
Altitude (Dimensions) ≤ 2000 m (amsl (above mean sea level))
Type (Ambient conditions) DIN rail module, two-section, divisible
Color (Ambient conditions) light gray
Response time tA (General) ≤ 25 ns
Depth (Key Commercial Data) 56.4 mm
Width (Key Commercial Data) 11.7 mm
EN type (Ambient conditions) T2
Height (Key Commercial Data) 44.8 mm
Nominal voltage UN (General) 240 V AC (TN)
TOV behavior at UT (General) 415 V AC (5 s / withstand mode)
Nominal frequency fN (General) 50 Hz (60 Hz)
Shock (operation) (Dimensions) 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Residual voltage Ures (General) ≤ 1.5 kV (at In)
Degree of protection (Dimensions) IP20
Mounting type (Ambient conditions) on base element
Vibration (operation) (Dimensions) 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Weight per Piece (excluding packing) 50.000 g
Housing material (Ambient conditions) PBT-FR
Voltage protection level Up (General) ≤ 1.5 kV
Connection method (Protective circuit) pluggable
Horizontal pitch (Key Commercial Data) 0.6 Div.
Maximum continuous voltage UC (General) 350 V AC
Mode of protection (Ambient conditions) L-N
Standards/regulations (Connection data) IEC 61643-11 2011
Degree of pollution (Ambient conditions) 2
Number of positions (Ambient conditions) 1
Ambient temperature (operation) (Dimensions) -40 °C ... 80 °C
IEC power supply system (Ambient conditions) TN
IEC test classification (Ambient conditions) II
Short-circuit current rating ISCCR (General) 25 kA
Max. backup fuse with branch wiring (General) 315 A AC (gG)
Permissible humidity (operation) (Dimensions) 5 % ... 95 %
Nominal discharge current In(8/20) µs (General) 20 kA
Maximum discharge current Imax(8/20) µs (General) 30 kA
Surge protection fault message (Ambient conditions) optical
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 80 °C
Flammability rating according to UL 94 (Ambient conditions) V-0

Product Description

Replacement connector for VAL-CP surge protection equipment with high power varistor with low leakage current.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top