Service time: Monday to Friday 9:00-18:00
UNO2-PS/1AC/24DC/480W - UNO2-PS/1AC/24DC/480W 2910105 PHOENIX CONTACT Primary-switched power supply unit, UNO POWER, Screw connectio..
In Stock Hot Product

UNO2-PS/1AC/24DC/480W

UNO2-PS/1AC/24DC/480W 2910105 PHOENIX CONTACT Primary-switched power supply unit, UNO POWER, Screw connectio..

$0.00 USD
3520 in stock
Key Specifications
GTIN: 4055626456652
Orderkey: 2910105
(General): IEC 61010-2-201
(Drawings):
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
GTIN 4055626456652
Orderkey 2910105
(General) IEC 61010-2-201
(Drawings)
(EMC data) For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
(Standards) 2 kV (Test Level 3 - asymmetrical)
Catalog page Page 268 (C-4-2019)
Packing unit 1 pc
Depth (Drawings) 125 mm
Width (Drawings) 59 mm
Country of origin TH (Thailand)
ETIM 5.0 (eCl@ss) EC002540
ETIM 6.0 (eCl@ss) EC002540
ETIM 7.0 (eCl@ss) EC002540
Height (Drawings) 130 mm
Input (Standards) 2 kV (Test Level 3 - symmetrical)
Diagram (Drawings)
Output (Standards) 1 kV (Test Level 2 - symmetrical)
Voltage (Standards) 230 V AC
Comments (Standards) Criterion B
Custom tariff number 85044030
(Ambient conditions) 2.4 kV AC (routine test)
China RoHS (EMC data) Environmentally Friendly Use Period = 25;
Frequency (Standards) 50 Hz
REACh SVHC (EMC data) Lead 7439-92-1
Criterion A (Standards) Normal operating behavior within the specified limits.
Criterion B (Standards) Temporary impairment to operational behavior that is corrected by the device itself.
Voltage dip (Standards) 0 %
Block diagram (Drawings)
Voltage dips (Standards) EN 61000-4-11
Noise emission (Standards) EN 55016
Additional text (Standards) Test Level 2
Climatic class (Dimensions) 3K3 (in acc. with EN 60721)
Frequency range (Standards) 0.15 MHz ... 80 MHz
Discharge in air (Standards) 8 kV (Test Level 3)
eCl@ss 8.0 (Classifications) 27049002
eCl@ss 9.0 (Classifications) 27040701
Contact discharge (Standards) 6 kV (Test Level 3)
Harmonic currents (Standards) EN 61000-3-2
Number of periods (Standards) 1 period
eCl@ss 11.0 (Classifications) 27040701
Dimensional drawing (Drawings)
Standard designation (General) Requirement of the semiconductor industry with regard to mains voltage dips
Efficiency (Ambient conditions) typ. 93 % (120 V AC)
Net weight (Ambient conditions) 1 kg
Standards/regulations (General) SEMI F47 - 0706 (185 V AC)
Test field strength (Standards) 10 V/m (Test Level 3)
eCl@ss 10.0.1 (Classifications) 27040701
Degree of pollution (Dimensions) 2
Installation height (Dimensions) ≤ 3000 m (> 2000 m, Derating: 10 %/1000 m)
Degree of protection (Dimensions) IP20
Low Voltage Directive (Standards) Conformance with Low Voltage Directive 2014/35/EC
Conducted interference (Standards) EN 61000-4-6
Electrostatic discharge (Standards) EN 61000-4-2
Fast transients (burst) (Standards) EN 61000-4-4
Conducted noise emission (Standards) EN 55016
Electromagnetic HF field (Standards) EN 61000-4-3
Weight per Piece (excluding packing) 1,240.000 g
Housing material (Ambient conditions) Aluminum (AlMg3) / sheet steel, zinc-plated
Protection class (Ambient conditions) I
Mounting position (Ambient conditions) horizontal DIN rail NS 35, EN 60715
Surge voltage load (surge) (Standards) EN 61000-4-5
Foot latch material (Ambient conditions) Sheet steel, zinc-plated
Degree of protection (Ambient conditions) IP20
Electromagnetic compatibility (Standards) Conformance with EMC Directive 2014/30/EU
Assembly instructions (Ambient conditions) alignable: 0 mm horizontally, 30 mm vertically
Ambient temperature (operation) (Dimensions) -25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K)
EMC requirements for noise immunity (General) EN 61000-6-2
MTBF (IEC 61709, SN 29500) (Ambient conditions) > 900000 h (25 °C)
Insulation voltage input / PE (Ambient conditions) 3.5 kV AC (type test)
Flammability rating according to UL 94 (Dimensions) V0 ()
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 85 °C
Insulation voltage input/output (Ambient conditions) 4 kV AC (type test)
Ambient temperature (start-up type tested) (Dimensions) -40 °C
Environmental protection directive (Ambient conditions) RoHS Directive 2011/65/EU
Max. permissible relative humidity (operation) (Dimensions) ≤ 95 % (at 25 °C, non-condensing)
Installation distance right/left (active, passive) (Drawings) 0 mm / 0 mm (POut≥50% )
Installation distance top/bottom (active, passive) (Drawings) 30 mm / 30 mm (POut≥50% )

Product Description

More details
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Technical Details

Block diagram

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top