Service time: Monday to Friday 9:00-18:00
TT-SLKK5-S- 12DC - TT-SLKK5-S- 12DC 2809597 PHOENIX CONTACT Surge protection device
In Stock Hot Product

TT-SLKK5-S- 12DC

TT-SLKK5-S- 12DC 2809597 PHOENIX CONTACT Surge protection device

$0.00 USD
4653 in stock
Key Specifications
GTIN: 4017918101275
Note: Made to Order (non-returnable)
Orderkey: 2809597
(General): C3 - 25 A
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
GTIN 4017918101275
Note Made to Order (non-returnable)
Orderkey 2809597
(General) C3 - 25 A
Catalog page Page 99 (C-6-2013)
Packing unit 50 pc
Country of origin DE (Germany)
Custom tariff number 85363030
Rated current (General) 32 A (50 °C)
Type (Ambient conditions) Single-level terminal block – separate PE connection
Color (Ambient conditions) black
Depth (Key Commercial Data) 69.5 mm
Width (Key Commercial Data) 6.2 mm
(Standards and Regulations) Lead 7439-92-1
Height (Key Commercial Data) 66.5 mm
Nominal voltage UN (General) 12 V DC
Residual current IPE (General) ≤ 5 µA
Capacity (line-earth) (General) 2.35 nF
VDE requirement class (General) C3
Degree of protection (Dimensions) IP20
IEC test classification (General) C1
Screw thread (Protective circuit) M3
Mounting type (Ambient conditions) DIN rail: 35 mm
Weight per Piece (excluding packing) 19.400 g
Housing material (Ambient conditions) PA
Stripping length (Protective circuit) 8 mm
Connection method (Protective circuit) Screw connection
REACh SVHC (Standards and Regulations) 4-Nonylphenol, ethoxylated
Response time tA(line-earth) (General) ≤ 1 ns
Tightening torque (Protective circuit) 0.5 Nm
Maximum continuous voltage UC (General) 13.6 V DC
Standards/regulations (Connection data) IEC 61643-21
Direction of action (Ambient conditions) Line-Earth Ground
Surge protection fault message (General) none
Connection method IN (Protective circuit) Screw terminal blocks
Impulse durability (line-earth) (General) C1 - 500 V / 250 A
Connection method OUT (Protective circuit) Screw terminal blocks
Standards/specifications (Connection data) IEC 61643-21 2000
Ambient temperature (operation) (Dimensions) -40 °C ... 85 °C
Residual voltage at In(line-earth) (General) ≤ 29 V
Operating effective current ICat UC (General) ≤ 5 µA
Conductor cross section AWG (Protective circuit) 24 ... 12
Conductor cross section solid (Protective circuit) 0.2 mm² ... 4 mm²
Total discharge current Itotal(8/20) µs (General) 346 A
Conductor cross section flexible (Protective circuit) 0.2 mm² ... 4 mm²
Flammability rating according to UL 94 (Ambient conditions) V-2
Nominal discharge current In(8/20) µs (line-earth) (General) 346 A
Nominal pulse current Ian (10/1000) µs (line-earth) (General) 67 A
Output voltage limitation at 1 kV/µs (line-earth) spike (General) ≤ 24 V
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system (General) typ. 1 MHz
Output voltage limitation at 1 kV/µs (line-earth) static (General) ≤ 19 V
Max. discharge current Imax(8/20) µs maximum (line-earth) (General) 346 A

Product Description

More details
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top