Key Specifications
: 10.3 mA (No load, mains operation)
Time: 316800 h
Color: red
Depth: 125 mm
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
10.3 mA (No load, mains operation)
Time 316800 h
Color red
Depth 125 mm
I/O/S asymmetrical
Input 2 kV (Test Level 3 - asymmetrical)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Width 35 mm
Height 130 mm
Output 2 kV (Test Level 3 - asymmetrical)
Signal 2 kV (Test Level 4 - asymmetrical)
Voltage 10 V (Test Level 3)
Comments Criterion A
Derating 60 °C ... 70 °C (2.5 %/K)
Duration 12 ms (SFB technology)
Interface IFS (Interface system data port)
Efficiency > 98 % (Mains operation, with charged energy storage)
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Hood version Galvanized sheet steel, free from chrome (VI)
Output power 120 W
Product type DC UPS
Screw thread M4
UL approvals UL Listed UL 508
Assembly note alignable: horizontal 5 mm, vertical 50 mm
Bridging time 28800 s
Buffer period 2 h (With battery module 12 AH)
IQ technology Yes
Input voltage 24 V DC
Mounting type DIN rail mounting
Climatic class 3K3 (in acc. with EN 60721)
Output voltage 24 V
Product family QUINT USV
Status display LED
Frequency range 80 MHz ... 1 GHz
Type of housing Aluminum (AlMg3)
Article revision 12
Charging current 0.2 A ... 1.36 A
Discharge in air 15 kV (Test Level 4)
Housing material Metal
Protection class III
Stripping length 7 mm
Connection method Pluggable screw connection
Contact discharge 8 kV (Test Level 4)
Mounting position horizontal DIN rail NS 35, EN 60715
Power dissipation 2.5 W (Mains operation)
Rail applications EN 50121-4
Network management Yes
Nominal voltage UN 24 V DC
Output description Relay (floating)
Types of signaling LED
Current consumption 9.4 A (maximum, mains operation)
Input voltage range 18 V DC ... 30 V DC
Test field strength 20 V/m
Connection in series no
Degree of protection IP20
Output current limit In mains mode according to connected upstream current limiting device
Output voltage range 18 V DC ... 30 V DC
POWER BOOST (IBoost) 7.5 A (-25 °C ... 40 °C)
End-of-charge voltage 24 V DC ... 29 V DC (temperature compensated)
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Standards/regulations EN 61000-4-2
Tightening torque max 0.6 Nm
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Connection in parallel yes, up to 2 modules with redundancy module
Fixed backup threshold ≤ 22 V DC
Input voltage range DC 18 V DC ... 30 V DC
Nominal capacity range 0.8 Ah ... 140 Ah
Nominal output voltage 24 V DC
Note on status display static on
Tightening torque, min 0.5 Nm
Continuous load current ≤ 100 mA
Temperature compensation 42 mV/K (preset)
Maximum switching voltage ≤ 30 V AC/DC
Signalization designation Power In OK
MTBF (IEC 61709, SN 29500) > 500000 h (25 °C)
Variable connect threshold 1 V/0.1 s
Nominal input voltage range 24 V DC
Nominal output current (IN) 5 A (-25 °C ... 50 °C)
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Selective Fuse Breaking (ISFB) 30 A (-25 °C ... 60 °C)
Voltage type of supply voltage DC
Ambient temperature (operation) -25 °C ... 70 °C
Battery presence check (cyclic) 60 s
Insulation voltage input/output 500 V DC
Conductor cross section AWG max. 12
Conductor cross section AWG min. 20
Installation distance right/left 5 mm / 5 mm
Installation distance top/bottom 50 mm / 50 mm
Temperature compensation (preset) 42 mV/K
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section, rigid min. 0.2 mm²
EMC requirements for noise emission EN 61000-6-3
EMC requirements for noise immunity EN 61000-6-1
Battery presence check/time interval 1 min.
Conductor cross section flexible max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Ambient temperature (storage/transport) -40 °C ... 85 °C
Insulation voltage input, output / housing 750 V DC
Max. permissible relative humidity (operation) ≤ 95 % (25 °C, non-condensing)
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)

Product Description

Uninterruptible power supply with IQ technology for rail mounting, input: 24 V DC, output: 24 V DC/5 A, including universal adapter for UTA 107/30 rail mounted
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide