Key Specifications
: < 2 % (change in load, dynamic 10 % ... 90 %)
Color: green
Depth: 125 mm
I/O/S: asymmetrical
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
< 2 % (change in load, dynamic 10 % ... 90 %)
Color green
Depth 125 mm
I/O/S asymmetrical
Input 2 kV (Test Level 3 - asymmetrical)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Width 32 mm
Height 130 mm
Output 2 kV (Test Level 3 - asymmetrical)
Signal 2 kV (Test Level 4 - asymmetrical)
Voltage 10 V (Test Level 3)
Comments Criterion B
Derating 60 °C ... 70 °C (2.5 %/K)
Rise time < 2 ms (UOUT(10 % ... 90 %))
Efficiency > 91.5 %
Input fuse 10 A (slow-blow, internal)
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Hood version Galvanized sheet steel, free from chrome (VI)
Output power 120 W
Screw thread M3
UL approvals UL/C-UL listed UL 508
Assembly note alignable: PN≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN<50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
Mounting type DIN rail mounting
Climatic class 3K3 (in acc. with EN 60721)
Inrush current < 5 A (typical)
Status display "DC OK" LED green
Frequency range 80 MHz ... 1 GHz
Residual ripple < 25 mVPP
Type of housing Aluminum (AlMg3)
Article revision 04
Discharge in air 15 kV (Test Level 4)
Housing material Metal
Number of phases 1.00
Protection class III
Stripping length 8 mm
Wide-range input no
Connection method Pluggable screw connection
Contact discharge 8 kV (Test Level 4)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Mounting position horizontal DIN rail NS 35, EN 60715
Rail applications EN 50121-4
Output description UOUT> 0.9 x UN: High signal
Protective circuit Transient surge protection; Varistor
Types of signaling LED
Current consumption 3.5 A (48 V DC)
Degree of pollution 2
Input voltage range 30 V DC ... 60 V DC
Test field strength 20 V/m (Test Level 3)
Connection in series yes
Degree of protection IP20
Mains buffering time > 14 ms (48 V DC)
Max. capacitive load unlimited
POWER BOOST (IBoost) 6.25 A (-25 °C ... 40 °C permanent, UOUT= 24 V DC )
Output characteristic U/I
Standards/regulations EN 61000-4-2
Tightening torque max 0.6 Nm
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Connection in parallel yes, for redundancy and increased capacity
Input voltage range DC 30 V DC ... 60 V DC
Maximum inrush current < 20 mA (short-circuit-proof)
Nominal output voltage 24 V DC ±1 %
Note on status display LED on
Tightening torque, min 0.5 Nm
Permissible backup fuse B10 B16
Switching voltage range 18 V DC ... 24 V DC
With protective coating no
Active current limitation Approximately 6.9 A
Standard - Safe isolation DIN VDE 0100-410
MTBF (IEC 61709, SN 29500) > 995000 h (40 °C)
Feedback voltage resistance 35 V DC
Nominal input voltage range 48 V DC
Nominal output current (IN) 5 A (-25 °C ... 60 °C)
Power loss nominal load max. 11 W
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Inrush current integral (I2t) < 0.2 A2s
Selective Fuse Breaking (ISFB) 30 A (12 ms)
Voltage type of supply voltage DC
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Insulation voltage input/output 1.5 kV (type test)
Conductor cross section AWG max. 12
Conductor cross section AWG min. 24
Installation distance right/left 0 mm / 0 mm (≤ 70 °C)
Installation distance top/bottom 50 mm / 50 mm (≤ 70 °C)
Magnetic circuit breaker tripping B2 / B4 / C2
Maximum no-load power dissipation 2.7 W
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section, rigid min. 0.2 mm²
EMC requirements for noise emission EN 61000-6-3
EMC requirements for noise immunity EN 61000-6-1
Peak switching voltages nominal load < 5 mVPP(20 MHz)
Conductor cross section flexible max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Standard – Safety extra-low voltage EN 60950-1 (SELV)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Recommended breaker for input protection 10 A ... 16 A (Characteristics B, C, D, K)
Installation distance right/left (active) 15 mm / 15 mm (≤ 70 °C)
Installation distance top/bottom (active) 50 mm / 50 mm (≤ 70 °C)
Ambient temperature (start-up type tested) -40 °C
Setting range of the output voltage (USet) 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Protection against overvoltage at the output (OVP) < 35 V DC
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)

Product Description

Primary switched QUINT DC/DC transformer for rail mounting with SFB (Selective Fuse Breaking) technology, input: 48 V DC, output: 24 V DC/5 A
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty