Key Specifications
: C2
Note: Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.
Type: DIN rail module, two-section, divisible
Color: black (RAL 9005)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
C2
Note Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.
Type DIN rail module, two-section, divisible
Color black (RAL 9005)
Depth 77.5 mm (incl. DIN rail 7.5 mm)
Width 17.7 mm
Height 91.1 mm
Altitude ≤ 4000 m (amsl)
Product type Surge protection for MCR technology
Screw thread M3
Mounting type DIN rail: 35 mm
Rated current 1000 mA (40 °C)
Product family PLUGTRAB IQ
Open side panel No
Article revision 08
Horizontal pitch 1 Div.
Housing material PA 6.6
Pollution degree 2
Connection method Screw connection
Tightening torque 0.5 Nm
Nominal voltage UN 24 V DC
Dimensional drawing
Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Resistance per path 1.2 Ω ±5 %
Capacity (Core-Core) typ. 2 nF
Degree of protection IP20
Overvoltage category III
Residual current IPE ≤ 2 µA (per signal circuit)
Wire pairs per module 1
IEC test classification C1
Standards/specifications IEC 61643-21
Input attenuation aE, sym. typ. 0.3 dB (≤ 270 kHz/150 Ω)
Max. required back-up fuse 1 A (FF)
Conductor cross section AWG 24 ... 12
Response time tA(line-line) ≤ 1 ns
Pulse reset time (line-line) ≤ 4000 ms
Response time tA(line-earth) ≤ 100 ns
Conductor cross section rigid 0.2 mm² ... 4 mm²
Maximum continuous voltage UC 30 V DC
Pulse reset time (line-earth) ≤ 2600 ms
Impulse durability (line-line) C1 - 1 kV / 500 A
Surge protection fault message Optical, multi-stage
Ambient temperature (operation) -40 °C ... 70 °C
Impulse durability (line-earth) C1 - 1 kV / 500 A
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Permissible humidity (operation) 5 % ... 95 %
Operating effective current ICat UC ≤ 1 mA (in the signal circuit)
Flammability rating according to UL 94 V-0
Voltage protection level Up(line-line) ≤ 80 V (C1 - 1 kV / 500 A)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Voltage protection level Up(line-earth) ≤ 600 V (C1 - 1 kV / 500 A)
Total discharge current Itotal(8/20) µs 20 kA
Voltage protection level Upstatic (line-line) ≤ 65 V (C1 - 1 kV / 500 A)
Nominal discharge current In(8/20) µs (line-line) 10 kA
Cut-off frequency fg (3 dB), sym. in 150 Ω system typ. 1.1 MHz
Nominal discharge current In(8/20) µs (line-ground) 10 kA
Pulse discharge current Iimp(10/350) µs (line-earth) 2.5 kA

Product Description

Surge protection, consisting of plug-in protection and base element, with multi-level status indication integrated into the module, for a 2-wire signal circuit driven free of earth potential, suitable
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top