Service time: Monday to Friday 9:00-18:00
PT 2-F-ST - PT 2-F-ST 2859000 PHOENIX CONTACT Surge protection plug
In Stock Hot Product

PT 2-F-ST

PT 2-F-ST 2859000 PHOENIX CONTACT Surge protection plug

$0.00 USD
4738 in stock
Key Specifications
GTIN: 4017918902452
Note: Made to Order (non-returnable)
Orderkey: 2859000
(General): D1 - 2.5 kA
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
GTIN 4017918902452
Note Made to Order (non-returnable)
Orderkey 2859000
(General) D1 - 2.5 kA
Catalog page Page 115 (C-4-2017)
Packing unit 10 pc
Country of origin DE (Germany)
(Connection data) EN 61643-21 2001 + A1:2009 + A2:2013
Custom tariff number 85363010
Altitude (Dimensions) ≤ 2000 m (amsl (above mean sea level))
Rated current (General) 2 A AC (80 °C)
Type (Ambient conditions) Male
Color (Ambient conditions) jet black RAL 9005
Depth (Key Commercial Data) 52 mm
Width (Key Commercial Data) 17.7 mm
Height (Key Commercial Data) 45 mm
Nominal voltage UN (General) 48 V AC
Residual current IPE (General) ≤ 4 µA
Resistance in series (General) 0 Ω
Capacity (line-earth) (General) typ. 2 pF
Degree of protection (Dimensions) IP20
IEC test classification (General) C1
Screw thread (Protective circuit) M3
Mounting type (Ambient conditions) on base element
Max. required back-up fuse (General) 2 A AC (T)
Weight per Piece (excluding packing) 16.120 g
Housing material (Ambient conditions) PA 6.6
Input attenuation aE, asym. (General) typ. 0.1 dB (≤ 1 MHz / 50 Ω)
Stripping length (Protective circuit) 8 mm
Connection method (Protective circuit) Screw connection (in connection with the base element)
Horizontal pitch (Key Commercial Data) 1 Div.
Response time tA(line-earth) (General) ≤ 100 ns
Tightening torque (Protective circuit) 0.5 Nm
Maximum continuous voltage UC (General) 60 V DC
Direction of action (Ambient conditions) Line-Earth Ground
Surge protection fault message (General) none
Impulse durability (line-earth) (General) C2 - 10 kV/5 kA
Standards/specifications (Connection data) IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
Complete module depth (Key Commercial Data) 65.5 mm
Complete module width (Key Commercial Data) 17.7 mm
Ambient temperature (operation) (Dimensions) -40 °C ... 85 °C
Complete module height (Key Commercial Data) 90 mm
Operating effective current ICat UC (General) ≤ 2 µA
Conductor cross section AWG (Protective circuit) 24 ... 12
Voltage protection level Up(line-earth) (General) ≤ 600 V (C2 - 10 kV / 5 kA)
Conductor cross section solid (Protective circuit) 0.2 mm² ... 4 mm²
Total discharge current Itotal(8/20) µs (General) 20 kA
Conductor cross section flexible (Protective circuit) 0.2 mm² ... 2.5 mm²
Voltage protection level Upstatic (line-earth) (General) ≤ 25 V (C2 - 10 kV / 5 kA)
Flammability rating according to UL 94 (Ambient conditions) V-0
Nominal discharge current In(8/20) µs (line-earth) (General) 20 kA
Pulse discharge current Iimp(10/350) µs (line-earth) (General) 5 kA
Output voltage limitation at 1 kV/µs (line-earth) spike (General) ≤ 600 V
Cut-off frequency fg (3 dB), asym. (GND) in 50 Ohm system (General) typ. 100 MHz
Output voltage limitation at 1 kV/µs (line-earth) static (General) ≤ 25 V
Arrester can be tested with CHECKMASTER from software version: (Ambient conditions) From SW rev. 1.10

Product Description

Plug-in surge protection for the base element, surge protection for two signal cables grounded on one side.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top