Service time: Monday to Friday 9:00-18:00
PT 1X2-12DC/FM-ST - PT 1X2-12DC/FM-ST 2920065 PHOENIX CONTACT Surge protection plug
In Stock Hot Product

PT 1X2-12DC/FM-ST

PT 1X2-12DC/FM-ST 2920065 PHOENIX CONTACT Surge protection plug

$0.00 USD
3382 in stock
Key Specifications
GTIN: 4046356153980
Note: Made to Order (non-returnable)
Orderkey: 2920065
(General): C3 - 100 A
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
GTIN 4046356153980
Note Made to Order (non-returnable)
Orderkey 2920065
(General) C3 - 100 A
Catalog page Page 90 (TT-2011)
Depth (Note) 52 mm
Packing unit 10 pc
Width (Note) 17.7 mm
Height (Note) 45 mm
Country of origin DE (Germany)
Custom tariff number 85363010
(Ambient conditions) IEC 60664-1
Horizontal pitch (Note) 1 Div.
Rated current (General) 450 mA (45°C)
Type (Ambient conditions) Male
Color (Ambient conditions) black
Complete module depth (Note) 65.5 mm
Complete module width (Note) 17.7 mm
Nominal voltage UN (General) 12 V DC
Complete module height (Note) 90 mm
Capacity (line-line) (General) typ. 3 nF
Residual current IPE (General) ≤ 2 µA (Directly grounded)
Resistance in series (General) 2.2 Ω ±10 % (7-8/11-12)
Capacity (line-earth) (General) typ. 4 pF
VDE requirement class (General) C1
Degree of protection (Dimensions) IP20
IEC test classification (General) C1
Screw thread (Protective circuit) M3
Mounting type (Ambient conditions) on base element
Input attenuation aE, sym. (General) typ. 0.5 dB (≤ 600 kHz / 50 Ω)
Max. required back-up fuse (General) 500 mA (T)
Weight per Piece (excluding packing) 27.100 g
Housing material (Ambient conditions) PA 6.6
Response time tA(line-line) (General) ≤ 1 ns
Stripping length (Protective circuit) 8 mm
Connection method (Protective circuit) Screw connection (in connection with the base element)
Response time tA(line-earth) (General) ≤ 100 ns
Tightening torque (Protective circuit) 0.8 Nm
Maximum continuous voltage UC (General) 13 V DC
Direction of action (Ambient conditions) Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Impulse durability (line-line) (General) C2 - 10 kV/5 kA
Surge protection fault message (General) Optical, remote indicator contact
Impulse durability (line-earth) (General) C2 - 10 kV/5 kA
Standards/specifications (Connection data) IEC 61643-21 2002
Residual voltage at In(line-line) (General) ≤ 18 V
Ambient temperature (operation) (Dimensions) -40 °C ... 85 °C
Operating effective current ICat UC (General) ≤ 5 µA
Utilization restriction (Key Commercial Data) EMC: class A product, see manufacturer's declaration in the download area
Conductor cross section AWG (Protective circuit) 24 ... 12
Voltage protection level Up(line-line) (General) ≤ 19 V (C1 - 500 V / 250 A)
Voltage protection level Up(line-earth) (General) ≤ 450 V (C2 - 10 kV / 5 kA)
Conductor cross section solid (Protective circuit) 0.2 mm² ... 4 mm²
Pulse discharge current Iimp(10/350) µs (General) 2.5 kA
Total discharge current Itotal(8/20) µs (General) 20 kA
Conductor cross section flexible (Protective circuit) 0.2 mm² ... 2.5 mm²
Flammability rating according to UL 94 (Ambient conditions) V-0
Alternating current carrying capacity (line-earth) (General) 5 A - 1 s
Cut-off frequency fg (3 dB), sym. in 50 Ohm system (General) typ. 3 MHz
Nominal discharge current In(8/20) µs (line-line) (General) 10 kA
Cut-off frequency fg (3 dB), sym. in 150 Ohm system (General) typ. 1 MHz
Nominal discharge current In(8/20) µs (line-earth) (General) 10 kA
Nominal pulse current Ian (10/1000) µs (line-line) (General) 70 A (25 °C / 1x)
Residual voltage with Ian (10/1000) µs (line-line) (General) ≤ 23 V
Output voltage limitation at 1 kV/µs (line-line) spike (General) ≤ 25 V
Output voltage limitation at 1 kV/µs (line-earth) spike (General) ≤ 450 V
Output voltage limitation at 1 kV/µs (line-line) static (General) ≤ 19 V
Max. discharge current Imax(8/20) µs maximum (line-line) (General) 10 kA
Standards for cearances and creepage distances (Ambient conditions) VDE 0110-1
Max. discharge current Imax(8/20) µs maximum (line-earth) (General) 10 kA

Product Description

Pluggable surge protection with diagnostic and status indication on the module and remote indication for a potential-free two-conductor signal circuit.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top