Service time: Monday to Friday 9:00-18:00
MNT-TELE S/WH - MNT-TELE S/WH 2880901 PHOENIX CONTACT Type 3 surge protection device
In Stock Hot Product

MNT-TELE S/WH

MNT-TELE S/WH 2880901 PHOENIX CONTACT Type 3 surge protection device

$0.00 USD
3492 in stock
Key Specifications
: C2
Note: 2011
Type: Attachment plug
Depth: 78 mm
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
C2
Note 2011
Type Attachment plug
Depth 78 mm
Width 63 mm
Height 103 mm
EN type T3
Altitude ≤ 2000 m (amsl)
Product type Device protection
Mounting type Plugging into the mains socket
Rated current 150 mA (25 °C)
Product family MAINTRAB
Number of ports One
Housing material PA 6
Pollution degree 2
Connection method RJ12
Nominal voltage UN 230/400 V AC (TN)
Dimensional drawing
Direction of action L/N-PE & Signal Line-Earth Ground
Insulating material PA 6
Capacity (Core-Core) typ. 1 nF
Combination wave UOC 4 kV
Degree of protection IP20 (Child-proofing)
Nominal frequency fN 50 Hz (60 Hz)
Overvoltage category III
Residual current IPE ≤ 5 µA
CTI value of material 400
Capacity (Core-Earth) typ. 5 pF
Rated load current IL 16 A (30 °C)
Response time tA(L-N) ≤ 25 ns
Wire pairs per module 1
Response time tA(L-PE) ≤ 100 ns
Response time tA(N-PE) ≤ 100 ns
IEC test classification C1
TOV behavior at UT(L-N) 335 V AC (5 s / withstand mode)
Standards/specifications IEC 61643-11
TOV behavior at UT(L-PE) 440 V AC (5 s / withstand mode)
TOV behavior at UT(N-PE) 1200 V AC (200 ms / safe failure mode)
Insulation resistance Riso ≥ 1 MΩ
Max. required back-up fuse 16 A (gG / B / C)
For country-specific use in NL, E, I, S, FIN, TR
Reference test voltage UREF 255 V AC
Response time tA(line-line) ≤ 25 ns
Pulse reset time (line-line) ≤ 15 ms
Response time tA(line-earth) ≤ 100 ns
Standby power consumption PC ≤ 1 VA
Energy absorption symmetrical 140 J (L-N)
Maximum continuous voltage UC 200 V DC
Enery absorption, asymmetrical 220 J (L(N)-PE)
Surge protection fault message optical
Ambient temperature (operation) -25 °C ... 75 °C
Residual voltage at Iamax, (PE) ≤ 1 kV (at 1 kA)
Permissible humidity (operation) 5 % ... 95 %
Residual voltage at Iamax, (L-N) ≤ 1 kV (at 1 kA)
Voltage protection level Up(L-N) ≤ 1.2 kV
Residual voltage at Iamax, (L-PE) ≤ 1 kV (at 1 kA)
Voltage protection level Up(L-PE) ≤ 1.5 kV
Voltage protection level Up(N-PE) ≤ 1.5 kV
Short-circuit current rating ISCCR 1.5 kA AC
Max. backup fuse with branch wiring 16 A (gG / B / C)
Operating effective current ICat UC ≤ 150 µA
Max. discharge current Imax(8/20) µs 2.5 kA
Flammability rating according to UL 94 V-0
Nominal discharge current In(8/20) µs 3 kA (> 5x)
Voltage protection level Up(line-line) ≤ 460 V (C2 - 1 kA)
Ambient temperature (storage/transport) -25 °C ... 75 °C
Voltage protection level Up(line-earth) ≤ 900 V (C2 - 2 kA)
Residual voltage at In(conductor-ground) ≤ 30 V
Total discharge current Itotal(8/20) µs 10 kA
Residual voltage at In(conductor-conductor) ≤ 500 V
Maximum continuous operating voltage UC(L-N) 275 V AC
Maximum continuous operating voltage UC(L-PE) 360 V AC
Maximum continuous operating voltage UC(N-PE) 360 V AC
Alternating current carrying capacity (line-line) 250 mA - 1 s
Alternating current carrying capacity (line-earth) 10 A - 1 s
Nominal discharge current In(8/20) µs (line-line) 1 kA
Nominal pulse current Ian (10/1000) µs (line-line) 35 A
Residual voltage with Ian (10/1000) µs (line-line) ≤ 35 V
Cut-off frequency fg (3 dB), sym. in 100 Ω system typ. 4 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ω system typ. 3 MHz
Cut-off frequency fg (3 dB), sym. in 600 Ω system typ. 700 kHz
Nominal discharge current In(8/20) µs (line-ground) 2.5 kA
Nominal pulse current Ian (10/1000) µs (line-earth) 200 A
Residual voltage with Ian (10/1000) µs (line-earth) ≤ 35 V
Output voltage limitation at 1 kV/µs (line-line) spike ≤ 360 V
Output voltage limitation at 1 kV/µs (line-earth) spike ≤ 900 V
Output voltage limitation at 1 kV/µs (line-line) static ≤ 360 V

Product Description

Socket attachment plug with surge protection for the power supply and signal connection of an end device with analog or digital telecommunications interface (VDSL up to 50 Mbps, on short paths (< 300
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top