Key Specifications
Note: Seal unused slots/connections to ensure the degree of protection.
Type: Block design
Depth: 71 mm
Width: 127 mm
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
Note Seal unused slots/connections to ensure the degree of protection.
Type Block design
Depth 71 mm
Width 127 mm
Height 67 mm
Ripple Max 3.6 VSSwithin the permissible voltage range
Input name Digital inputs
Output name Digital outputs
Product type I/O component
Mounting type Wall mounting
Output voltage 24 V DC
Product family Ruggedline
Supply current typ. 80 mA (plus sensor current)
Supply voltage 24 V DC
No. of channels 6
Number of inputs 4
Connection method Optic fiber (polymer fiber 980/1000 µm)
Number of outputs 2
Nominal load, lamp 12 W
Note on dimensions with bus connection plugs and mounting panel
Protective circuit Electronic short-circuit/overload protection for each group
Transmission speed 2 Mbps
Nominal load, ohmic 12 W
Degree of protection IP65/IP67
Supply voltage range 18.5 V DC ... 32 V DC (including ripple)
Total sensor current max. 200 mA
Transmission physics FO
Connection technology 2-, 3-, 4-conductor
Overcurrent shut-down min. 0.7 A
Behavior with overload Auto restart
Nominal output voltage 24 V
Nominal load, inductive 12 VA (1.2 H, 48 Ω)
Air pressure (operation) 860 hPa ... 1080 hPa (up to 1500 m above sea level)
Input voltage range "0" signal 0 V DC ... 5 V DC
Input voltage range "1" signal 11 V DC ... 30 V DC
Ambient temperature (operation) 0 °C ... 55 °C
Air pressure (storage/transport) 660 hPa ... 1080 hPa (up to 3500 m above sea level)
Behavior with inductive overload Output can be destroyed
Output current when switched off max. 100 µA
Output voltage when switched off max. 1 V
Permissible humidity (operation) 100 %
Typical input current per channel 3 mA
Delay at signal change from 0 to 1 3 ms
Delay at signal change from 1 to 0 3 ms
Maximum output current per channel 500 mA
Ambient temperature (storage/transport) -25 °C ... 70 °C
Permissible humidity (storage/transport) 95 % (non-condensing)
Test voltage: Between bus logic and outputs 500 V AC, 50 Hz, 1 min.
Output current with ground connection interrupt when switched off max. 25 mA

Product Description

Digital input/output equipment for INTERBUS; Fibre optic technology with 2 Mbaud, four inputs (24 V DC), two outputs (24 V DC, 0.5 A), sensor/actuator connection via 5-pole M12 female connectors, robu
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top