FLT-SEC-P-T1-264/50-P - FLT-SEC-P-T1-264/50-P 2907391 PHOENIX CONTACT Type 1 surge protection plug
In Stock Hot Product

FLT-SEC-P-T1-264/50-P

FLT-SEC-P-T1-264/50-P 2907391 PHOENIX CONTACT Type 1 surge protection plug

$0.00 USD
4128 in stock
Key Specifications
GTIN: 4055626197210
Note: Made to Order (non-returnable)
Orderkey: 2907391
(General): 760 V AC (120 min / withstand mode)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
GTIN 4055626197210
Note Made to Order (non-returnable)
Orderkey 2907391
(General) 760 V AC (120 min / withstand mode)
Catalog page Page 34 (C-4-2017)
Packing unit 5 pc
Country of origin DE (Germany)
(Connection data) L-G
(UL specifications) EN 61643-11 2012
Custom tariff number 85363010
(Ambient conditions) PBT-FR
Altitude (Dimensions) ≤ 2000 m (amsl (above mean sea level))
Minimum order quantity 10 pc
Type (Ambient conditions) Male
Color (Ambient conditions) light grey RAL 7035
Response time tA (General) ≤ 100 ns
SPD Type (Connection data) 1CA
Depth (Key Commercial Data) 59.4 mm
Width (Key Commercial Data) 35.5 mm
EN type (Ambient conditions) T1 / T2
Height (Key Commercial Data) 46.6 mm
Nominal voltage UN (General) 240 V AC (TN)
TOV behavior at UT (General) 415 V AC (5 s / withstand mode)
Nom. voltage (Connection data) 240 V AC
Nominal frequency fN (General) 50 Hz (60 Hz)
Shock (operation) (Dimensions) 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Residual voltage Ures (General) ≤ 2.5 kV (at In)
Degree of protection (Dimensions) IP20
Mounting type (Ambient conditions) on base element
Vibration (operation) (Dimensions) 5g (5 - 500 Hz/2.5 h/X, Y, Z)
Nominal frequency (Connection data) 50/60 Hz
Mode of protection (Connection data) L-N
Weight per Piece (excluding packing) 259.900 g
Housing material (Ambient conditions) PA 6.6-FR 20% GF
Voltage protection level Up (General) ≤ 2.5 kV
Connection method (Protective circuit) pluggable
Horizontal pitch (Key Commercial Data) 2 Div.
REACh SVHC (Standards and Regulations) Lead 7439-92-1
Maximum continuous voltage UC (General) 264 V AC
Mode of protection (Ambient conditions) L-N
Degree of pollution (Ambient conditions) 2
Number of positions (Ambient conditions) 1
Standards/regulations (UL specifications) IEC 61643-11 2011
Power distribution system (Connection data) Single phase
Ambient temperature (operation) (Dimensions) -40 °C ... 80 °C
IEC power supply system (Ambient conditions) TT
IEC test classification (Ambient conditions) I / II
Short-circuit current rating ISCCR (General) 50 kA
Follow current interrupt rating Ifi (General) 50 kA
Max. backup fuse with branch wiring (General) 500 A (gG)
Permissible humidity (operation) (Dimensions) 5 % ... 95 %
Nominal discharge current In (Connection data) 20 kA
Voltage protection rating VPR (Connection data) 1500 V
Nominal discharge current In(8/20) µs (General) 50 kA
Maximum discharge current Imax(8/20) µs (General) 100 kA
Surge protection fault message (Ambient conditions) optical
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 80 °C
Short-circuit current rating (SCCR) (Connection data) 50 kA
Impulse discharge current (10/350) µs, charge (General) 25 As
Flammability rating according to UL 94 (Ambient conditions) V-0
Maximum continuous operating voltage MCOV (Connection data) 264 V AC
Front of wave sparkover voltage at 6 kV (1.2/50) µs (General) ≤ 2.5 kV
Impulse discharge current (10/350) µs, peak value limp (General) 50 kA
Impulse discharge current (10/350) µs, specific energy (General) 625 kJ/Ω

Product Description

Replacement connector for the lightning current arresters of the FLASHTRAB SEC PLUS 264 product series, for the L-N and L-PEN sections.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide