Key Specifications
GTIN: 4055626176000
Orderkey: 2907259
(General): 1640 V AC (200 ms / safe failure mode)
Catalog page: Page 28 (C-4-2017)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
GTIN 4055626176000
Orderkey 2907259
(General) 1640 V AC (200 ms / safe failure mode)
Catalog page Page 28 (C-4-2017)
Packing unit 1 pc
Country of origin DE (Germany)
(Connection data) EN 61643-11 2012
Custom tariff number 85363030
(Ambient conditions) PBT-FR
(Protective circuit) 1 A DC (30 V DC)
Altitude (Dimensions) ≤ 2000 m (amsl (above mean sea level))
Type (Ambient conditions) DIN rail module, two-section, divisible
Color (Ambient conditions) light grey RAL 7035
Response time tA (General) ≤ 100 ns
Depth (Key Commercial Data) 74.5 mm
Width (Key Commercial Data) 35.5 mm
(Standards and Regulations) Lead 7439-92-1
EN type (Ambient conditions) T1 / T2
Height (Key Commercial Data) 167 mm
Nominal voltage UN (General) 400 V AC (TN)
TOV behavior at UT (General) 580 V AC (5 s / withstand mode)
Nominal frequency fN (General) 50 Hz (60 Hz)
Residual current IPE (General) ≤ 5 µA
Residual voltage Ures (General) ≤ 2.5 kV (at In)
Degree of protection (Dimensions) IP20 (only when all terminal points are used)
Screw thread (Protective circuit) M2
Mounting type (Ambient conditions) DIN rail: 35 mm
Weight per Piece (excluding packing) 660.000 g
Housing material (Ambient conditions) PA 6.6-FR 20% GF
Stripping length (Protective circuit) 7 mm
Voltage protection level Up (General) ≤ 2.5 kV
Connection method (Protective circuit) Plug-in/screw connection via COMBICON
Horizontal pitch (Key Commercial Data) 2 Div.
Operating current (Protective circuit) 10 mA AC ... 1 A AC
Operating voltage (Protective circuit) 12 V AC ... 250 V AC
REACh SVHC (Standards and Regulations) N,N-dimethylacetamide 127-19-5
Tightening torque (Protective circuit) 0.25 Nm
Maximum continuous voltage UC (General) 440 V AC
Mode of protection (Ambient conditions) L-N
Standards/regulations (Connection data) IEC 61643-11 2011
Switching function (Protective circuit) PDT contact
Degree of pollution (Ambient conditions) 2
Number of positions (Ambient conditions) 1
Screw thread (Indicator/remote signaling) M5
Ambient temperature (operation) (Dimensions) -40 °C ... 80 °C
IEC power supply system (Ambient conditions) TN-C
IEC test classification (Ambient conditions) I / II
Short-circuit current rating ISCCR (General) 50 kA
Follow current interrupt rating Ifi (General) 50 kA
Permissible humidity (operation) (Dimensions) 5 % ... 95 %
Stripping length (Indicator/remote signaling) 18 mm
Connection method (Indicator/remote signaling) Fork-type cable lug
Tightening torque (Indicator/remote signaling) 4.5 Nm
Conductor cross section AWG (Protective circuit) 28 ... 16
Nominal discharge current In(8/20) µs (General) 25 kA
Conductor cross section solid (Protective circuit) 0.14 mm² ... 1.5 mm²
Maximum discharge current Imax(8/20) µs (General) 50 kA
Surge protection fault message (Ambient conditions) Optical, remote indicator contact
Ambient temperature (storage/transport) (Dimensions) -40 °C ... 80 °C
Conductor cross section flexible (Protective circuit) 0.14 mm² ... 1.5 mm²
Conductor cross section AWG (Indicator/remote signaling) 13 ... 2
Impulse discharge current (10/350) µs, charge (General) 12.5 As
Conductor cross section solid (Indicator/remote signaling) 2.5 mm² ... 35 mm²
Flammability rating according to UL 94 (Ambient conditions) V-0
Conductor cross section flexible (Indicator/remote signaling) 1.5 mm² ... 16 mm²
Front of wave sparkover voltage at 6 kV (1.2/50) µs (General) ≤ 2.5 kV
Impulse discharge current (10/350) µs, peak value limp (General) 25 kA
Impulse discharge current (10/350) µs, specific energy (General) 160 kJ/Ω

Product Description

Plug-in lightning current arrester, according to type 1/class I, with fuse resistant to momentary overcurrents, for single-phase power supply networks with PE and N placed in combination on a conducto
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified