ELR 3-230AC/500AC- 2 - ELR 3-230AC/500AC- 2 2297206 PHOENIX CONTACT Solid-state contactor
In Stock Hot Product

ELR 3-230AC/500AC- 2

ELR 3-230AC/500AC- 2 2297206 PHOENIX CONTACT Solid-state contactor

$0.00 USD
3988 in stock
Key Specifications
: 60 Hz
FLA: 2 A (at 500 V, AC Resistance)
SCCR: 5 kA (20 A RK5 (standard fault) fuse)
Depth: 114.5 mm
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
60 Hz
FLA 2 A (at 500 V, AC Resistance)
SCCR 5 kA (20 A RK5 (standard fault) fuse)
Depth 114.5 mm
Width 40 mm
Height 99 mm
Input name Control input right/left
Certificate NMFT.E323771
Product type Solid-state contactor
Screw thread M3
Assembly note Can be aligned with spacing = 20 mm
Mounting type DIN rail mounting
Surge current 200 A (t = 10 ms)
Operating mode 100% operating factor
Status display LED (yellow)
Leakage current 6 mA
Mains frequency 50 Hz
Max. load value 250 A2s
Article revision 05
Error indication Red LED
Number of phases 3
Residual voltage < 1.5 V
Stripping length 8 mm
Connection method Screw connection
Mounting position Vertical (horizontal DIN rail)
Tightening torque 0.5 Nm ... 0.6 Nm
Load current range 100 mA ... 2 A (see to derating)
Protective circuit Surge protection; Varistor
Degree of pollution 2
Rated surge voltage 6 kV
Switching frequency ≤ 1 Hz
Switching threshold 48 V AC (“0” signal)
Degree of protection IP20
Overvoltage category III
Peak offstate voltage 1200 V
Standards/regulations DIN EN 50178
Operating voltage range 48 V AC ... 575 V AC
Rated insulation voltage 500 V
Surge voltage protection > 575 V AC
Triggering voltage range 92 V AC ... 253 V AC
Rated actuating current IC 12.5 mA
Rated actuating voltage UC 230 V AC
Rated operating voltage Ue 500 V AC
Conductor cross section AWG 24 ... 14
Test voltage (Input/output) 5 kVrms(50 Hz, 60 s)
Conductor cross section rigid 0.2 mm² ... 2.5 mm²
Ambient temperature (operation) -25 °C ... 70 °C
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Rated operating current at AC-51 2 A
Rated operating current at AC-53a 2 A
Voltage range with reference to UC 0.4 ... 1.1
Ambient temperature (storage/transport) -25 °C ... 70 °C
Insulation characteristics between the control input voltage to the main circuit Basic insulation

Product Description

Three-phase semiconductor contactor with 230 V AC input, 2 A output current, zero voltage switch, optionally with thermal fuse
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide