Service time: Monday to Friday 9:00-18:00
CTM ISDN - CTM ISDN 2838555 PHOENIX CONTACT Surge protection plug
In Stock Hot Product

CTM ISDN

CTM ISDN 2838555 PHOENIX CONTACT Surge protection plug

$0.00 USD
4997 in stock
Key Specifications
GTIN: 4017918819583
Note: Made to Order (non-returnable)
Orderkey: 2838555
(General): D1 - 1 kA
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
GTIN 4017918819583
Note Made to Order (non-returnable)
Orderkey 2838555
(General) D1 - 1 kA
Catalog page Page 167 (C-4-2017)
Packing unit 10 pc
Country of origin DE (Germany)
Custom tariff number 85363010
(Ambient conditions) IEC 60664-1
Rated current (General) 1.5 A (25 °C)
Type (Ambient conditions) LSA-PLUS module
Color (Ambient conditions) black
Depth (Key Commercial Data) 53.5 mm
Width (Key Commercial Data) 9.5 mm
Height (Key Commercial Data) 21 mm
Nominal voltage UN (General) 6 V DC
Capacity (line-line) (General) 25 pF (f=1 MHz / VR= 0 V)
Residual current IPE (General) ≤ 2 µA
VDE requirement class (General) B2
Degree of protection (Dimensions) IP20
IEC test classification (General) B2
Mounting type (Ambient conditions) On CT-TERMIBLOCK and LSA-PLUS disconnect strip
Connection method (Connection data) Spring contact
Input attenuation aE, sym. (General) 0.3 dB (≤ 45 MHz)
Weight per Piece (excluding packing) 9.090 g
Housing material (Ambient conditions) PA
Response time tA(line-line) (General) ≤ 500 ns
Connection method (Protective circuit) can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips
Response time tA(line-earth) (General) ≤ 100 ns
Maximum continuous voltage UC (General) ± 6 V DC
Degree of pollution (Ambient conditions) 2
Direction of action (Ambient conditions) Line-Line & Line-Earth Ground
Impulse durability (line-line) (General) C2 - 4 kV / 2 kA
Number of positions (Ambient conditions) 2
Surge protection fault message (General) none
Connection method IN (Protective circuit) COMTRAB plug-in system
Impulse durability (line-earth) (General) C2 - 4 kV/2 kA
Overvoltage category (Ambient conditions) II
Connection method OUT (Protective circuit) COMTRAB plug-in system
Connection technology (Protective circuit) LSA-PLUS
Residual voltage at In(line-line) (General) ≤ 32 V
Ambient temperature (operation) (Dimensions) -25 °C ... 75 °C
Residual voltage at In(line-earth) (General) ≤ 55 V
Voltage protection level Up(line-line) (General) ≤ 35 V (C1 - 700 V/350 A)
Voltage protection level Up(line-earth) (General) ≤ 700 V (C2 - 10 kV/5 kA, spike)
Total discharge current Itotal(8/20) µs (General) 10 kA
Total discharge current Itotal(10/350) µs (General) 2.5 kA
Standards/regulations (Connection, equipotential bonding) IEC 61643-21
Flammability rating according to UL 94 (Ambient conditions) V-0
Nominal discharge current In(8/20) µs (line-line) (General) 350 A
Standards/specifications (Connection, equipotential bonding) IEC 61643-21 2000
Cut-off frequency fg (3 dB), sym. in 100 Ohm system (General) ≥ 100 MHz
Nominal discharge current In(8/20) µs (line-earth) (General) 5 kA
Nominal pulse current Ian (10/1000) µs (line-line) (General) 100 A
Residual voltage with Ian (10/1000) µs (line-line) (General) ≤ 18 V
Residual voltage with Ian (10/1000) µs (line-earth) (General) ≤ 12 V
Pulse discharge current Iimp(10/350) µs (line-earth) (General) 1 kA
Output voltage limitation at 1 kV/µs (line-line) spike (General) ≤ 60 V
Output voltage limitation at 1 kV/µs (line-earth) spike (General) ≤ 700 V
Output voltage limitation at 1 kV/µs (line-line) static (General) ≤ 15 V
Output voltage limitation at 1 kV/µs (line-earth) static (General) ≤ 700 V
Standards for cearances and creepage distances (Ambient conditions) DIN VDE 0110-1
Max. discharge current Imax(8/20) µs maximum (line-earth) (General) 10 kA (in total)
Arrester can be tested with CHECKMASTER from software version: (Ambient conditions) From SW rev. 1.10

Product Description

LSA-PLUS (COMTRAB CTM) plug-in protection protection for a pair of conductors of an ISDN So interface.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top