Service time: Monday to Friday 9:00-18:00
CN-LAMBDA/4-2.2-SB - CN-LAMBDA/4-2.2-SB 2800025 PHOENIX CONTACT Surge protection device
In Stock Hot Product

CN-LAMBDA/4-2.2-SB

CN-LAMBDA/4-2.2-SB 2800025 PHOENIX CONTACT Surge protection device

$0.00 USD
3772 in stock
Key Specifications
: C3
Note: 2005
Type: Attachment plug
Depth: 89 mm
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
C3
Note 2005
Type Attachment plug
Depth 89 mm
Width 26.1 mm
Height 66 mm
Product type Surge protection for transceiver systems
Mounting type Connection-specific intermediate plugging
Seal material Silicon
Frequency range 0.82 GHz ... 2.2 GHz
Open side panel No
Housing material Brass (CuZn)
Connection method N connector 50 Ω
Direction of action Line-Shield/Earth Ground
Degree of protection IP68
Standards/regulations IEC 61643-21
VDE requirement class C2
IEC test classification C2
Housing surface material Ni
Inner conductor material BeCu
Insulation body material PTFE
Standards/specifications IEC 61643-21
Input attenuation aE, asym. typ. 0.05 dB (≤ 0.15 dB)
Surge protection fault message none
Total surge current (8/20) µs 60 kA
Ambient temperature (operation) -40 °C ... 90 °C
Impulse durability (line-earth) C2 - 10 kV / 5 kA
Impulse durability (line-shield) C2 - 10 kV/5 kA
Inner conductor surface material Gold
Total surge current (10/350) µs 20 kA
Voltage protection level Up(line-earth) ≤ 12 V (6 kV / 3 kA)
Voltage protection level Up(line-shield) ≤ 12 V (6 kV / 3 kA)
Pulse discharge current Iimp(10/350) µs 20 kA
Voltage standing wave ratio VSWR in a 50 Ω system typ. 1.10 (≤ 1.20 (0.82 GHz...2.2 GHz))
Nominal discharge current In(8/20) µs (line-ground) 50 kA
Nominal discharge current In(8/20) µs (line-shield) 50 kA
Permissible HF power Pmaxat VSWR = xx (50 ohm system) ≤ 500 W
Pulse discharge current Iimp(10/350) µs (line-earth) 20 kA
Impulse discharge current (10/350) µs, peak value limp 20 kA
Output voltage limitation at 1 kV/µs (line-earth) spike ≤ 12 V (6 kV / 3 kA)
Output voltage limitation at 1 kV/µs (line-earth) static ≤ 12 V (6 kV / 3 kA)
Output voltage limitation at 1 kV/µs (line-shield) spike ≤ 12 V (6 kV / 3 kA)
Max. discharge current Imax(8/20) µs maximum (line-earth) 60 kA
Output voltage limitation at 1 kV/µs (line-shield) static ≤ 12 V (6 kV / 3 kA)
Max. discharge current Imax(8/20) µs maximum (line-shield) 60 kA

Product Description

Attachment plug with Lambda/4 technology as surge protection for coaxial signal interfaces. Connection: N connectors plug/socket
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top