Key Specifications
: 18 V DC ... 30 V DC
Fuse: electronic
Note: Interference emission
Type: Male
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
18 V DC ... 30 V DC
Fuse electronic
Note Interference emission
Type Male
Color gray (RAL 7042)
Depth 52 mm
Width 12.3 mm
Height 45 mm
General When mounted in rows without convection cooling, the nominal device current should only be led to a maximum of 80% due to the thermal effect during continuous operation (100% operating factor).Special precautionary measures must be taken in systems or machines, to prevent components from restarting (e.g., use of a safety PLC).Parallel connection of multiple circuit breakers is not permitted.
Product type Device circuit breakers
Voltage drop 100 mV (at IN)
Humidity test 96 h, 95 % RH, 40 °C
Mounting type on base element
Shutdown time 200 ms (see time/current characteristic curve)
Identification UL Listed UL 508
Product family CB E
No. of channels 1
Switch-on delay typ. 2 ms
Tripping method E (electronic)
Article revision 03
Pollution degree 2
Connection method pluggable
Fail-safe element 6 A DC
Operating voltage 24 V DC
Power dissipation 0.81 W (Nominal operation)
Nominal current IN 4 A
Dielectric strength max. 30 V DC (Load circuit)
Dimensional drawing
Number of positions 1
Rated surge voltage 0.5 kV
Degree of protection IP30 (Actuation area)
Max. capacitive load 20000 µF
Required backup fuse not required, integrated failsafe element
Standard designation EMV
Temperature derating 4 A (at 50 °C)
Complete module depth 77.3 mm
Complete module width 12.3 mm
Vibration (operation) 3g (according to IEC 60068-2-6, Test Fc)
Complete module height 90 mm
Contact connection type floating signal contact
Undervoltage switch-off < 14 V (typ. OFF)
Standards/specifications EN 61000-6-3
Active current limitation typ. 1.25 x IN
Closed circuit current I0 typ. 8 mA (When switched on)
MTBF (IEC 61709, SN 29500) 8320000 h (at 25 °C with 80 % load)
Max. operating current Imax 0.5 A
Minimum operating current Imin 10 mA
Ambient temperature (operation) -25 °C ... 50 °C (non-condensing)
Maximum operating voltage UmaxDC 30 V DC
Minimum operating voltage UminDC 10 V DC
Flammability rating according to UL 94 V-0
Ambient temperature (storage/transport) -40 °C ... 70 °C

Product Description

Interruption. Protec. Electronic, 1 pole, active current limiter, 1 NO contact, connector for base element.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top