Service time: Monday to Friday 9:00-18:00
AXL F DO16/2 2H - AXL F DO16/2 2H 1027904 PHOENIX CONTACT I/O module
In Stock Hot Product

AXL F DO16/2 2H

AXL F DO16/2 2H 1027904 PHOENIX CONTACT I/O module

$0.00 USD
3533 in stock
Key Specifications
: max. 1 per second (with inductive load)
Type: block modular
Depth: 54 mm
Width: 35 mm
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

Parameter Value
max. 1 per second (with inductive load)
Type block modular
Depth 54 mm
Width 35 mm
Height 129.9 mm
Load min. 10 kΩ
Output name Digital outputs
Current draw max. 60 mA
Product type I/O component
Signal delay max. 100 µs (when switched on)
Mounting type DIN rail mounting
Output voltage 24 V DC
Product family Axioline F
Supply voltage 5 V DC (via bus base module)
Connection name Axioline F connector
Article revision 02
Pollution degree 2 (IEC 60664-1, EN 60664-1)
Protection class III (IEC 61140, EN 61140, VDE 0140-1)
Stripping length 8 mm
Connection method Bus base module
Mounting position any (no temperature derating)
Number of outputs 16
Scope of delivery including bus base module and Axioline F connectors
Input address area 0 Byte
Nominal load, lamp max. 12 W (at nominal voltage)
Note on dimensions The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).
Protective circuit Short-circuit protection, overload protection of the outputs; electronic
Transmission speed 100 Mbps
Dimensional drawing
Nominal load, ohmic max. 12 W (48 Ω, with nominal voltage)
Note on application Only for industrial use
Output address area 2 Byte
Switching frequency max. 10000 per second (with at least 50 mA load current)
Degree of protection IP20
Number of interfaces 2
Overvoltage category II (IEC 60664-1, EN 60664-1)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Connection technology 2-conductor
Overcurrent shut-down as of 0.7 A
Behavior with overload Shutdown with automatic restart
Nominal output voltage 24 V DC
Nominal load, inductive max. 12 VA (1.2 H, 48 Ω, with nominal voltage)
Required parameter data 1 Byte
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Conductor cross section AWG 24 ... 16
Required configuration data 6 Byte
Conductor cross section rigid 0.2 mm² ... 1.5 mm²
Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor cross section, rigid 0.2 mm² ... 1.5 mm²
Ambient temperature (operation) -25 °C ... 60 °C
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Behavior with inductive overload Output can be destroyed
Conductor cross section flexible 0.2 mm² ... 1.5 mm²
Output current when switched off max. 300 µA
Output voltage when switched off max. 1 V
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Conductor cross section, flexible 0.2 mm² ... 1.5 mm²
Maximum output current per module 8 A (provide external protection)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
Reverse voltage resistance to short pulses limited protection up to 0.5 A for 1 s
Maximum power dissipation for nominal condition 1.6 W
Test voltage: 24 V supply (I/O) / functional ground 500 V AC, 50 Hz, 1 min.
Limitation of the voltage induced on circuit interruption -32.8 V ... -15 V
Output current with ground connection interrupt when switched off < 1 mA
Test voltage: 5 V supply of the local bus (UBus) / functional ground 500 V AC, 50 Hz, 1 min.
Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os) 500 V AC, 50 Hz, 1 min.

Product Description

AxiolineF, Digital output module, Digital outputs:16, 24 VDC, 500 mA, connection technology:2 conductors, transmission speed on the local bus:100 MBit/s, protection index: IP20, including bus socket m
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top